Maxge 2P residual current device, 25A, 30mA. Class F. 10kA

68,93€

TAXES INC.
  • Number of poles: 2 poles
  • Rated current (In): 25 amps
  • Sensitivity: 30 mA
  • Class F: detects intermittent, continuous, pulsating and mixed-frequency leakage currents
  • Operating voltage: 240V AC, 50Hz
  • Breaking capacity: 10 kA
  • Local status signalling
  • Window for circuit marker
  • Terminal connection for copper cables: up to 25 mm² flexible / 35 mm² rigid
  • Tightening torque: 2.5 Nm
  • Non-operational leakage current: 0.5 × IΔn
  • Dimensions: 36mm (18mm per pole)
  • Allows attachment of accessories and control gear
  • Insulation voltage (Ui) 500 V
  • Impulse voltage (Uimp) 4kV
  • IP20 protection rating (IP40 in an enclosure)
  • Double insulation class 2
- +
Disponible para la venta · Plazo de entrega según stock de la referencia
Product
Finance your purchase with Cetelem
Reference: EPR2F025030 Categories: ,

Details of the Maxge 2P residual current device, 25A, 30mA. Class F. 10kA

Maxge 2P residual current device, 25A, 30mA. Class F. 10kA – EPR2F025030

The Maxge 2P, 25A, 30mA, Class F, 10kA residual current circuit breaker (RCCB) is a bipolar Class F residual current circuit breaker designed to protect people against indirect contact in single-phase installations.

Class F residual current devices (RCDs) detect, in addition to the sinusoidal and pulsating continuous faults detected by Class A devices, mixed-frequency fault currents generated by equipment with single-phase power electronics: frequency converters, heat pumps and inverter-type air conditioners, washing machines, swimming pool pumps and inverters. In such circuits, a Class AC or A residual current device may fail to detect faults or trip prematurely; Class F devices prevent both of these problems.

With a rated current of 25 A, a sensitivity of 30 mA and a breaking capacity of 10 kA, it is suitable for domestic, commercial and industrial applications.

Technical specifications

  • Number of poles: 2 poles
  • Rated current (In): 25 amps
  • Sensitivity: 30 mA
  • Class F: detects intermittent, continuous, pulsating and mixed-frequency leakage currents
  • Operating voltage: 240V AC, 50Hz
  • Breaking capacity: 10 kA
  • Local status signalling
  • Window for circuit marker
  • Terminal connection for copper cables: up to 25 mm² flexible / 35 mm² rigid
  • Tightening torque: 2.5 Nm
  • Non-operational leakage current: 0.5 × IΔn
  • Dimensions: 36mm (18mm per pole)
  • Allows attachment of accessories and control gear
  • Insulation voltage (Ui) 500 V
  • Impulse voltage (Uimp) 4kV
  • IP20 protection rating (IP40 in an enclosure)
  • Double insulation class 2

Applications

Residual current protection for circuits supplying heat pumps, inverter air conditioning systems, variable-speed pumps and other single-phase electronic loads. Please note that the RCD does not provide protection against overloads: it must be used in conjunction with the appropriate circuit breaker.

Weight and dimensions

Weight 0,25 kg
Dimensions 6,66 × 3,6 × 8,15 cm

User feedback

Reviews

There are no reviews yet.

Be the first to review “Diferencial Maxge 2P, 25A, 30mA. Clase F. 10kA”

Your email address will not be published. Required fields are marked *

Delivery deadlines

At FVComponentes.com we have stock of the references with the highest turnover, however our catalogue is so wide and economical because we work with many of the references on request. This means that the usual delivery time of 2-4 working days can be extended to 1-2 weeks + subsequent shipment by us. Thanks to this, we can offer very competitive and attractive prices to our customers that are difficult to match. If you wish, you can write to us via the chat on the website, call us at 968 97 83 01 or write to us at comercial@fvcomponentes.com to check if we have stock or the delivery time of the component you wish to purchase before finalising your order.