VE.Bus errors on the Victron, MultiPlus and Quattro: what each code means and how to resolve them

The Victron investor-loaders (MultiPlus, MultiPlus-II, Quattro) report faults in two ways: by means of the Front LED and, if there is a GX device (Cerbo GX, Ekrano GX), via a VE.Bus error code visible on the GX screen, in VRM and in VictronConnect. This guide covers both and adds error code #67 relating to communication with the BMS.

LED alarms (without the GX device)

LEDStatusReasonWhat to do
Low battery (flashing)NoticeThe battery voltage is approaching the cut-off thresholdReduce the load or charge the battery (solar, mains, generator)
Low battery (permanent)OffVoltage below the DC cut-off (default 9.3 / 18.6 / 37.2 V)The inverter restarts when the voltage rises. If this happens every night, the battery is undersized or at the end of its life.
Overload (flashing)NoticeFuel consumption close to maximum powerCollect parcels
Overload (fixed)OffOverload or short circuit at the AC outputSwitch off all loads, restart the system and switch them on one by one. Take care with motor and compressor start-ups (3–5 times their rated current)
Temperature (flashing)NoticeHigh internal temperatureImproves ventilation; leave a 10 cm gap all round
Temperature (fixed)OffOvertemperatureWait for it to cool down; if the fan isn’t turning, contact SAT
Low battery + Overload (alternating flashes)OffDC ripple too highBattery cables that are too long or too thin, or loose terminals. Check the connections and tighten them
Fixed Bulk + Absorption + FloatBlockadeInternal errorRestart. If the problem persists, contact support

With VictronConnect (Bluetooth via the VE.Bus Smart Dongle or MK3-USB cable), you will be able to view these alarms as text messages, along with the history.

VE.Bus error codes (with GX)

CodeMeaningSolution
VE.Bus error 1A device has lost communication in a parallel/three-phase systemCheck the RJ45 cables between units (they must be straight-through CAT5 cables, not crossover cables) and ensure that none of the units are switched off
Error 2New unit detected or unit removedRun VE.Bus System Configurator or VE.Bus Quick Configure again
Error 3Not all devices are present, or they are not all configured in the same wayConfigure all units using the same file and the same firmware version
Error 4There is no more than one device on the bus (the system is configured as parallel, but only one is visible)Cables or power supply for the second unit
Error 5Overvoltage at the AC outputIt is usually a problem with a single unit; replace
Error 6Error in the DDC programmeRestart; if the problem persists, contact SAT
Error 7Slave drive with different firmware or from a different generationUpdate the firmware so that they all match
Error 8Incorrect bus hardware or cablingCheck RJ45 connectors and terminators
Error 9Internal communication failureSAT
Error 10System synchronisation failedRestart all units at the same time
Error 11Mains or battery relay not found / ripple problemLoose AC-in wiring or unsuitable DC cables
Error 12Incorrect system configurationReconfigure using System Configurator
Error 14Device installation errorReconfigure or update the firmware
Error 15AC output overcurrentOverload in a phase or unit
Error 16Output voltage out of rangeCheck that all units are set to the same voltage (230 V)
Error 17Phase loss / master unit not connectedIn a three-phase system, one phase is missing: cables or unit switched off
Error 18AC output overvoltageLoad with energy recovery (motor, other inverter); check the installation
Error 22This device cannot operate as a slaveSettings: switch between master and slave
Error 24System switching protectionRestart
Error 25Incompatible firmwareUpdate
Error 26Internal rulingSAT

General rule: in parallel or three-phase systems, All units must have the same firmware and the same configuration file. Most errors 1–4 and 7 are caused by failing to comply with this.

Error #67: BMS connection lost

This appears in Cerbo GX when CAN communication with the BMS of a managed battery has been lost (Pylontech, Pytes, ZYC, BYD LV, Victron, Lynx BMS). With DVCC active, the inverter and MPPT units stop charging for safety reasons.

  • Check the Type A CAN cable (VE.Can to CAN-bus BMS) between the GX and the master battery. It’s a specialised cable, not a standard RJ45; you can find it at Victron cables.
  • Check that the correct port on the GX is set to 500 kbit/s “CAN-bus BMS (LV)” (Settings → Services).
  • Check that the master battery is switched on and that the CAN terminator is at the other end of the bus.
  • Following a power cut, some batteries take a minute to resume posting; the error clears itself.

Further details at DVCC: what it is and how to set it up.

Other common alarms in VRM

  • Low battery voltage / High voltage: VEConfigure thresholds or BMS limits. Check the battery profile.
  • Grid lost: The inverter has rejected the grid due to voltage/frequency being out of range or because the grid code does not match (Spain: “Other / UNE 217002” in accordance with applicable regulations).
  • Inverter overload: See also: LED Overload.
  • VE.Bus system: Charge current limited by low temperature: The (lithium) battery temperature is below 5 °C and the BMS blocks charging. This is a standard safety measure.

Reset procedure

  1. 1. Switch off the AC loads.
  2. 2. Set the inverter switch to OFF and open the battery isolator switch.
  3. 3. Wait 2 minutes.
  4. 4. Close the isolator, switch on the inverter and then the GX.
  5. 5. Check in VRM that the error has been resolved.

For the reference connection diagram, see Victron MultiPlus diagram.

We are authorised Victron Energy installers and provide free technical support for equipment purchased from FV Componentes. If the problem persists, please open a ticket at Technical support including the model, serial number and the link to your VRM installation. You can find diagrams and parameters on our Victron Resource Centre.