Victron Smart Battery Protect 48V-100A
123,71€
TAXES INC.
Maximum continuous load current: 100A
Peak current (for 30 seconds): 250A
Working voltage range: 24 -70V
Disponible para la venta · Plazo de entrega según stock de la referencia
Finance your purchase with Cetelem
GTIN: 8719076041252
Reference:
BPR110048000
Categories: Solar batteries, Accessories for solar batteries, Battery protectors
Details of the Victron Smart Battery Protect 48V-100A
Features of the Smart Battery Protect 48V-100A - BPR110048000
Protects the battery from excessive discharging and can be used as a system on/off switch
The Smart Battery Protect 48V-100A - BPR110048000 disconnects non-essential loads from the battery before it is fully discharged (which would damage the battery) or before it runs out of sufficient charge to start the engine. The on/off input can be used as a system on/off switch.
Bluetooth: easy programming
When programming the Smart BatteryProtect via Bluetooth, the desired activation/deactivation levels can be defined. Alternatively, the programming pin can be used to define one of the nine activation/deactivation levels (see manual).
If necessary, Bluetooth can be disabled.
A special configuration for Li-Ion batteries
In this mode, BatteryProtect can be controlled via the VE.Bus BMS.
Note: BatteryProtect can also be used as a charging switch between a battery charger and a Li-ion battery. See the connection diagram in the manual.
Ultra-low power consumption
This is important in the case of Li-Ion batteries, especially after a low voltage disconnection.
Please refer to our Li-Ion battery datasheet and the manual for the Li-Ion battery. VE.Bus BMS for more information.
Overvoltage protection
To prevent damage to sensitive loads due to overvoltage, the load is switched off when the DC voltage exceeds 16.3V or 32.6V respectively.
Fireproofing
Without relays but with MOSFET switches, therefore no sparks.
Delayed alarm output
The alarm output is activated if the battery voltage drops below the preset cut-off level for more than 12 seconds. Therefore, starting the engine will not activate the alarm. The alarm output is a short-circuit proof open collector output to the negative (minus) rail, with a maximum current of 50 mA. Normally, the alarm output is used to activate an acoustic signal, an LED or a relay.
Disconnection and delayed reconnection of the load
The load shall be disconnected 90 seconds after the battery voltage drops below the preset level. If the battery voltage rises back towards the switch-on threshold within this period of time (after e.g. the engine has been started), the load shall not be disconnected.
The charge will be reconnected 30 seconds after the battery voltage has risen above the
default reconnection.
Datasheet Victron Smart Battery Protect 48V-100A - BPR110048000
View Victron Smart Battery Protect 48V-100A - BPR110048000 datasheet
Weight and dimensions
| Weight | 1,300 kg |
|---|---|
| Dimensions | 19 × 7 × 7 cm |